Bus SCS
SCS is an acronym for "Sistema Cablaggio Semplificato". It uses a fieldbus network protocol and has applications in the field of home automation and building automation. It is used mainly in bTicino and Legrand installations.
General features
An SCS bus is based on a sheathed twisted pair formed of two flexible conductors; these are braided and unshielded with isolation 300/500V, SELV as double isolation is required – according to the rules adopted by CEI. The bus is unpolarized, devices are required to support the DC power supply in both polarity.Wiring
Two kind of wiring are possible:- Free cabling were a mix of bus and star topology are present, better for old houses
- Star wiring were all devices are connected to the switch rack, better for new houses
Communication
- Electricity supply via 27 Vdc
- Data with a frequency clock of 9600 Hz
- Sound
- Video
Functions
Through the SCS bus you have the following functions:- Light control
- Automation
- Sound diffusion
- Energy management
- Thermoregulation
- Video intercom
- Alarm system
Configuration
All devices connected to SCS bus must be manually configured, no autolearn is possible, apart Alarm system and extenders. Configuration assign an address and an operating mode. Two kind of configurations are possible:- Physical - using numbered jumpers with different values resistor
- Virtual - using a configuration software connected with an ethernet gateway. In this case the address and operating mode are written in a non volatile memory in every device. Applying a physical jumper override the virtual configuration wiping the memory.
Addressing details
digits | Physical | Virtual | note |
A | 0-9 | 0-10 | 11 rooms max in a single SCS domain |
PL | 1-9 | 0-15 | A=0,PL=0 is forbidden, so 175 loads are addressable in a single SCS domain |
GR | 1-9 | 0-255 | group |
Writing physical addresses use 2 digits. Writing virtual addresses use 4 digits.
In big houses and buildings, SCS address extension is possible, were different address domains are connected via some bridges. Only some kind of messages can cross a bridge.
Here the values of physical configuration jumpers:
marking | color | value | code | description |
--- | infinite | --- | default to virtual | |
0 | green | 4659 kOhm | 3501/0 | digit |
1 | green | 817 kOhm | 3501/1 | digit |
2 | green | 673 kOhm | 3501/2 | digit |
3 | green | 556 kOhm | 3501/3 | digit |
4 | green | 471 kOhm | 3501/4 | digit |
5 | green | 389 kOhm | 3501/5 | digit |
6 | green | 329 kOhm | 3501/6 | digit |
7 | green | 271 kOhm | 3501/7 | digit |
8 | green | 218 kOhm | 3501/8 | digit |
9 | green | 179 kOhm | 3501/9 | digit |
GEN | blue | 100 kOhm | 3501/GEN | general broadcast |
GR | blue | 68 kOhm | 3501/GR | group broadcast |
AMB | blue | 33 kOhm | 3501/AMB | room broadcast |
AUX | blue | 2.2 kOhm | 3501/AUX | auxiliary channel |
ON | blue | 120 kOhm | 3501/ON | send ON command |
OFF | blue | 150 kOhm | 3501/OFF | send OFF command |
0/1 | blue | 180 kOhm | 3501/01 | send toggle command |
PUL | blue | 2.2 kOhm | 3501/PUL | button command monostable |
SLA | blue | 120 kOhm | 3501/SLA | slave of another control |
CEN | blue | 33 kOhm | 3501/CEN | advanced scenarios mode |
↑↓ | blue | 100 kOhm | 3501/T | up/down for shutters |
↑↓M | blue | 68 kOhm | 3501/TM | up/down for shutters monostable |
Certifications
Devices connected to the SCS bus are -certified and comply with these product standards.Integration
You can interact with the SCS bus through a gateway and an open high-level protocol called OpenWebNet. Two kind of gateway exist:These gateways are bidirectional; they translate SCS frames into OpenWebNet frames, and the other way round.
The open protocol OpenWebNet shared by community, let everybody to build software that interact with SCS devices. SCS protocol is a proprietary bTicino protocol. Interaction with other field bus must happen only writing software that use OpenWebNet.