A circulating water plant or circulating water system is an arrangement of flow of water in fossil-fuel power station, chemical plants and in oil refineries. The system is required because various industrial process plants uses heat exchanger, and also for active fire protection measures. In chemical plants, for example in caustic soda production, water is needed in bulk quantity for preparation of brine. The circulating water system in any plant consists of a circulator pump, which develops an appropriate hydraulic head, and pipelines to circulate the water in the entire plant.

System description

Circulating water pumps

Circulating water systems are normally of the wet pit type, but for sea water circulation, both the wet pit type and the concrete volute type are employed. In some industries, one or two stand-by pumps are also connected parallel to CW pumps. It is recommended that these pumps must be constantly driven by constant speed squirrel cage induction motors. CW pumps are designed as per IS:9137, standards of the Hydraulic Institute, USA or equivalent.

Cooling tower

In the present era, mechanical induced draft–type cooling towers are employed in cooling of water. Performance testing of cooling towers shall be carried
out as per ATC-105 at a time when the atmospheric conditions are within the permissible limits of deviation from the design conditions. As guidelines of Central Electricity Authority, two mechanical draft cooling towers Or one natural draft cooling tower must be established for each 500 MW unit in power plants. The cooling towers are designed as per Cooling Tower Institute codes.

CW treatment system

Some coastal power stations or chemical plants intake water from sea for condenser cooling. They either use closed cycle cooling by using cooling towers or once through cooling. Selection of type of system is based on the thermal pollution effect on sea water and techno-economics based on the distance of power station from the coast and cost of pumping sea water. Due to high salt concentration, it is necessary for circulating water make up.

Mechanical description of CW plants

Source:
Source:
Sr No.IS CODESpecification
1IS: 804Rectangular pressed steel tanks
2IS: 1239Mild steel tubes, tubular & other wrought steel fittings
3IS: 1520Horizontal, centrifugal pumps for clear, cold fresh water
4IS: 1536Centrifugally cast iron pressure pipes for water, gas and
sewage
5IS: 1537Vertically cast iron pressure pipes for water, gas and sewage
6IS: 1710Vertical turbine pumps for clear, cold fresh water
7IS: 2002Steel plates for boilers
8IS: 2062structural steel
9IS: 2594Horizontal mild steel welded storage tanks
10IS: 2825Code for unfired pressure vessels
11IS: 3589Electrical welded pipes for water, gas & sewage
12IS: 3832Hand-operated chain pulley block
13IS: 4682Code of practice for lining of vessels and equipment for
chemical processes-rubber lining
14IS: 5120Technical requirements for rotodynamic special purpose
pumps
15IS: 5639Pumps handling chemicals and corrosive liquids
16IS: 5659Pumps for process water
17IS: 6393Steel pipe flanges
18IS: 6547Electric chain hoist
19BS: 5155Cast iron & carbon steel butterfly valves for general purpose
20AWWA-C-504Rubber seated butterfly valves