EN 16034


EN 16034 refers to a set of European standards which specify the technical performance characteristics for fire resisting and/or smoke control products, or better known in common language as fire/smoke doors or fire/smoke proof doors.
Compliance with this standard requires to fulfill the requirements of the Construction Product Regulation for construction products, which are placed on the EU market with the intention to become permanent parts of a construction.
The primary purpose of the CPR is to remove technical barriers to trade for product manufacturers within the Internal market through the development and adoption of common European technical specifications.
With the publication of EN 16034 conflicting national standards shall be withdrawn within a transitional period of 3 years. Product manufacturers can sell their products throughout Europe by complying with a single common specification recognised and accepted by all Member States, rather than having to test and comply with different national standards in each of them.
EN 16034 shall be implemented on a national level by national standardization bodies. Any conflicting national standards and / or national regulations have to be withdrawn latest when the co-existence period ends. The national editions of the standard receive the code of the national standardization body as prefix - for example DIN EN 16034 in Germany or UNI EN 16034 in Italy.
Products which are covered by EN 16034 have to be CE marked when placed on the market. CE marking enables free trade within all Member States. This is a major change as the affixing of the CE marking under the provisions of the old Construction Products Directive which has been replaced by the Construction Products Regulation was wrongly considered to be voluntary.

Rumors & News

As of October 10th 2018 prEN 14351-2 has been approved. The CEN the following dates regarding its publication:
where DAV refers to the date when the definitive text in the official language versions of an approved norm is distributed by the Central Secretariat, DAO refers to the latest date by which the existence of a European norm has to be announced at the national level, DOP refers to the latest date by which a European norm has to be implemented at national level by publication and DOW refers to the date by which national standards conflicting with a European norm have to be withdrawn. Especially the two dates DOP and DOW are interesting. The first will indicate when this new norm will in effect start its validity and the end of the coexistence period. The second date gives a good indication of how long this coexistence period will be In between the two dates both norms will coexist and both will need to be accepted by national authorities.

Interpretation of current situation

Most fire rated doors are used as internal doors. Given that EN 16034 can only be used in conjunction with other standards and given that the standard for internal doors is a work in progress the applicability date of 1 November 2019 will not change anything for the sector. Most fire rated doors currently still cannot be CE marked.
It is important to understand that the fire resisting and/or smoke control product is defined as doorset including any frame or guide, door leaf or leaves, rolling or folding curtain, etc., which is provided to give a fire resisting and/or smoke control capability when used for the closing of permanent openings in fire resisting separating elements, including any side panel, vision panel, flush over panel, transom panel and/or glazing together with the building hardware and any seals which form the assembly.

History

In 1994 the European Commission has invited the European Standardization bodies CEN and CENELEC to draw up a common European standard for fire and smoke proof doors. In 2015 the final version has been published under the standard code EN 16034 on the Official Journal of the European Union.

Scope

This European Standard identifies safety and performance requirements applicable to all fire resisting and/or smoke control products intended to be used in fire and/or smoke compartmentation and/or escape routes, which are either:
and either:
and completed:
It is important to understand that the fire resisting and/or smoke control product is defined as doorset including any frame or guide, door leaf or leaves, rolling or folding curtain, etc., which is provided to give a fire resisting and/or smoke control capability when used for the closing of permanent openings in fire resisting separating elements, including any side panel, vision panel, flush over panel, transom panel and/or glazing together with the building hardware and any seals which form the assembly.

Exclusions

This European Standard does not cover:
EN 16034 covers several essential characteristics related to the intended use of the construction product which are in particular:
All characteristics covered by this standard shall be determined with tests performed by an independent third party under the responsibility of a Notified Product Certification Body responsible for the interpretation and classification of the obtained test results.
Before the resistance to fire and/or smoke control the sample shall undergo a pre-test conditioning which is performed with:
After which, the various characteristics are evaluated:
CharacteristicTest standardClassification StandardClasses
FireEN 1634-1EN 13501-2E, EI1, EI2, EW + minutes
SmokeEN 1634-3EN 13501-2Sa, S200
Ability to releaseEN 1634-1 or EN 1634-3
Durability of the ability to releaseEN 1155 or EN 14637
Self-closing and durability of self-closingEN 1191 or EN 12605 EN 13501-2C + class 1-5

Procedure

Doors, gates and windows covered by EN 16034 are subject to system 1 of the Assessment and Verification of Constancy of Performance which means that the manufacturer in addition to the mentioned test and classification process is also under the surveillance of a Notified Surveillance Body responsible for the continuous surveillance and assessment of the Factory Production Control.

Initial Type Testing (ITT)

The manufacturer shall decide the use of his product. On this basis the Notified Product Certification Body will set a testing program which must be absolved successfully at a Notified Testing Laboratory resulting in a test report for each performed test. The Notified Testing Laboratory can but must not be identical to the NPC.
The achieved results are then interpreted and classified by the NPC and eventually extended by the use of the "direct" and "extended field of application" in order to allow for different dimensions, use of different hardware, etc.

Factory Production Control (FPC)

After the successful testing and assessment of the product the Notified Product Certification Body inspects the manufacturing plant and assesses the Factory Production Control system. If successful, the NPC may issue a "Certificate of Constancy of Performance" which forms the basis of the "Declaration of Performance" allowing the manufacturer to CE mark his products.
The manufacturer is furthermore responsible for testing further samples taken directly from the manufacturing plant to keep and maintain his "Certificate of Constancy of Performance" valid and to be able to continue to CE mark his products.

Classification report according to EN 13501-2

This report classifies the products based on the tests carried out, describes in details the components used and defines the boundaries of the product system with the "Field of Direct Application". The field of direct application lists the possible substitutions of components and deviations from the tested models. The field of direct application is very limited and allows modifications only to a strict extend.

EXAP report (extended field of application)

The EXAP report according to EN 15269-series defines the permitted extended variations of tested products from the tested specimens. The detailed rules for each appropriate material selection are defined in the relevant part of EN 15269-series.
Currently the following EXAPs are available or in preparation:
StandardDescriptionStatus of standard
EN 15269-1General requirementsPublished
EN 15269-2Hinged and pivoted steel doorsetsPublished
EN 15269-3Hinged and pivoted timber doorsetsPublished
prEN 15269-4Glass doorsProject
EN 15269-5Glass doors with metal framesPublished
prEN 15269-6Sliding timber doorsPublished
EN 15269-7Sliding steel doorsPublished
prEN 15269-8Folding timber doorsProject
prEN 15269-9Folding steel doorsProject
EN 15269-10Steel rolling shutterPublished
prEN 15269-11Operable fabric curtainsProject
EN 15269-20Smoke control doorsPublished

Cascading

To allow a "reuse" of the tested products the initial manufacturer can collaborate under a contract with "system providers" and delegate/outsource/franchise the production to them. Given that fire and smoke products are covered by AVCP system 1, the system provider has to undergo the Factory Production Control and the Continuous surveillance by an Notified Surveillance Body himself. Practically the system provider can avoid to do the initial type testing reusing the classification reports and extended application reports from the original manufacturer.

CE Marking

Products certified according to EN 16034 in combination with either EN 14351-1, EN 13241 and EN 16361 can be CE marked with the proper CE marking symbol.
The CE marking logo shall be affixed before the product is placed on the market together with the following information:
  1. the notified product certification body
  2. the name of the manufacturer
  3. the address of the manufacturer
  4. the last two digits of the year, when the certificate was obtained
  5. the reference number of the declaration of performance
  6. the dated reference to the applied harmonized standard/s
  7. the unique identification code of the product
  8. the intended use of the product
  9. the classes declared

    Declaration of Performance (DoP)

EN 16034 requires the distribution of a Declaration of Performance, to which every customer or user shall have access.
The DoP lists all essential characteristic of the product as required by EN 16034. The manufacturer shall at least declare one characteristic with a result.
Other characteristics can be declared as NPD.
DoPs are to be provided either in paper form or by electronic means in the language/s of the member state with every product delivered. The declaration of performance for products with fire resisting and/or smoke control characteristics shall contain at least the following details:

Normative references

The European test series for fire resisting doorsets are based on the test standard EN 1634-1, the series of test standards EN 1363 and the classification standard EN 13501-2.
The US tests for Fire rated doors are based on the NFPA 252 "Standard Methods of Fire Tests of Door Assemblies", the UL 10B "Fire Tests of Door Assemblies" and the UL 10C "Positive Pressure Fire Tests of Door Assemblies".
Large differences exist in opening directions to be tested, permitted wall types, surface temperatures permitted and sustained flaming allowances. Another major difference is the treatment of the exchangeability of components such as locks, hinges, and frame types. The EN standard basically requires each combination to be tested as a whole, where as UL is satisfied with the single component being tested independently from the door assembly. Further the EN standard differs in its treatment of the extension of dimensions from the UL standard. EN allows for only limited dimensional extensions, but requires in such cases a surplus of test time and better gap values. Whereas the UL Standard does not allow an increase of the dimension of the tested door, you can decrease the dimension without any restriction. Last but not least, UL requires at the end of the fire exposure a hose stream test, where water from a hose is directed to the tested assembly. No water shall penetrate and the door shall withstand the impact. The EN standard does not mention anything similar.

Differences in furnace time / temperature curve

The furnace time / temperature curves differ between the standards UL 10B and EN 1363-1 in that the UL standard focuses most of its rigour around the 20th minute. During the period of 10 to 30 minutes, the furnace temperature is slightly higher according to the UL standard, before and after that, the furnace temperature required by the EN Standard is higher.
The permitted percentile error quote in the curve's average furnace temperature is more stringent according to the UL Standard until the 20th minute, after that the EN standard is more severe.
Test periodNFPA 252 and UL 10BEN 1363-1
5 to 20 minutes10.0%15.0 - 10.0%
21 to 60 minutes10.0%9.5 - 2.51%
61 to 120 minutes7.5%2.5%
more than 120 minutes5.0%2.5%

Difference in the neutral pressure requirement

The neutral pressure requirements for furnaces according EN 1363-1 are stricter than the pressure criteria requirements of UL 10C. According to the EN standard, the furnace is operated so that the neutral pressure plane is established at 500 mm above notional floor level. Irrespective of this, the pressure at the top of the test specimen shall at no time exceed 20 Pa.
For UL 10C, "the neural plane of the furnace is to be established at a maximum of 40 inches up from the bottom of the test assembly. The pressure that is maintained over the top one-third of the door assembly is not to exceed 0.08 inch H2O over any portion of the test sample."
For UL 10B, the pressure in the furnace chamber is to be 0 +/-0.01 inches H2O at the top of the door.

Difference in opening directions to be tested

For insulated steel doors EN 1634-1 requires testing in both opening directions, whereas UL 10C only requires test orientation into the furnace.

Permitted wall types

The EN standard introduces the concept of standard supporting constructions. These are the constructions into which the test specimen is allowed to be built. The available standard supporting constructions are:
Given that these different wall types are of different rigidities and perform differently in fire conditions, the EN standard requires that the certificate of fired doors indicates for what wall type it has been tested. The UL Standard does not specify any such supporting construction types.

Integrity and surface temperatures

The UL standard provides that the unexposed surface temperatures be recorded only for the first 30 minutes of the test. The fire doors are then rated as temperature rise doors for 250 °F, 450 °F or 650 °F, respectively 121,11º degrees, 232,22º degrees and 343,33º degrees Celsius.
The EN standard requests the integrity criteria of the door to be expressed in completed minutes for which the test specimen continues to maintain its separating function during the test without developing temperatures above the initial average tempera¬ture on its unexposed sur¬face which either:
The purpose of average unexposed face temperature measurement is to determine the general level of insulation of the test specimen while ignoring particular hot spots. The purpose of maximum unexposed face temperature measurement is to determine the level of insulation at those locations where higher temperatures are expected to occur. To understand the importance of surface temperature go to youtube and search for "7Afz5sy2808".

Difference in flaming measurement

The EN 1363-1 standard requires that the specimen continues to maintain its separating function during the test without either:
The UL 10B Standard expresses the following concerning the flaming:
Whereas the UL 10C Standard states:
UL allows an individual composition of the door set from various components such as hinges, locks, frames, door leaves etc. as long as every single component has satisfied the UL standard and been tested individually as such. This is not true for the EN standard. Even though for each component there is a separate test standard available, which the single hardware component must satisfy, the EN standard allows only for the tested composition of components. Therefore exchanging hinges, locks, steel sheet thicknesses, etc. is generally not possible without additional tests.

Hose Stream Test

Contrary to the EN Standard, the UL Standards 10B and 10C requires a Hose Stream Test, which measures integrity of specimens after exposure to fire. This includes that immediately within 3 minutes after the termination of the fire resistance test, the tested door is to start to be subjected to the impact, erosion, and cooling effects of a hose stream directed ?rst at the bottom center of the assembly and then at all parts of the exposed surface. This can cause penetration of the assembly, breakage and dislodgement of hardware or glazing.