Short circuit ratio


Short circuit ratio or SCR is a measure of the stability of an electromechanical generator. It is the ratio of field current required to produce rated armature voltage at open circuit to the field current required to produce the rated armature current at short circuit.
The SCR can be calculated for each point on a grid. Where the SCR is above 1, a grid has good grid strength and will be less subject to variations in frequency and can provide more short circuit current.

Generator SCR

The larger the SCR, the smaller is alternator reactance and inductance Ld. This is result of larger air gaps in generator design. It results in to Machine loosely coupled to grid and its response will be slow. This increases the machines’ stability while operating on grid, but simultaneously will increase the short circuit current delivery capability of the machine and subsequently higher machine size and its cost. Typical values of SCR for Hydro alternators may be in the range of 1 to 1.5.
Conversely, smaller the SCR, then larger is alternators reactance, the larger is Ld. It is a result of small air gaps in machine design. Machines are tightly coupled to grid and their response will be fast. This reduces the machine’s stability while operating on grid and will reduce the short circuit current delivery capability, smaller machine size, and lower cost subsequently. Typical values of SCR for turbo alternators may be in the range of 0.45 to 0.9.

Impact on grid

The SCR can be calculated for each point on an electrical grid. A point on a grid having number of machines with an SCR above a number between 1 and 1.5 has less vulnerability to voltage instability. Hence, such grid is known strong grid or power system. A power system having lower SCR has more vulnerability to grid voltage instability. Hence such grid or system known as weak grid or power system.
Grid strength can be increased by installing synchronous condensers.